4.Entire List of PROG Menu – Setup Parameters
STAR
415.0
415.0
SET
SYS
V.PRI
V.SEC
415.0
415.0
0100
V.PRI
V.SEC
A.PRI
415.0
100.0
5.000
V.SEC
A.PRI
A.SEC
0100
5.000
123
A.PRI
A.SEC
LABL
5.000
123
3D
A.SEC
LABL
VA.Fn
123
3D
AUTO
LABL
VA.Fn
d.SEL
15
9600
EVN.1
d.PRD
BAUD
PRTY
Default Setup values are give in BOLD
*Changing these values while the device is in use, is not recommended.
SET= This menu has the entire PROG menu. The
user programmable parameters are listed here
SYS= Power system's configuration*:
STAR
, DELTA
V.PRI= Voltage primary winding (PT), line-line*
Input range: 100 v to 999 kv (
415.0
)
V.SEC= Voltage secondary winding (PT), line-line*
Input range: 50 v to 530 v (
415.0
)
A.PRI= Current primary winding (CT)*
Input range: 1 A to 99 kA (
100.0
)
A.SEC= Current secondary winding (CT)*
Input range: 1 A to 7.5 A (
5.000
)
LABL= Phase labeling
Choose from:
123
, RYB, RST, PQR, ABC
VA.FN= VA function selection*
Set the VA function to:
3D
, ARTH
F.S%= Full scale %
Set the full scale between1 to 100:
100
POLE= Number of poles for RPM
Choose from: 2,
4
,6,8,10,12,14,16
9600
EVN.1
1.000
BAUD
PRTY
ID
EVN.1
1.000
100.0
PRTY
ID
F.S
1.000
100.0
Wh
ID
F.S
O.F
100.0
Wh
4.000
F.S
O.F
POLE
Wh
4.000
O.F
POLE
d.SEL= Demand selection*:
auto
, user
d.PAR= Demand parameter*:
VA
, W
d.PRd= Demand period: 5,10,
15
,20,25,30
Baud= Baud rate : 1200, 2400, 4800,
9600
, 19200.
Id = RS485 Device ID number:
001
to 247. (Evn.1 =
Even. 1 stop bit)
4.000POLE
Prty = Parity & Stop bit settings:
EVn.1
, EVn.2,
Odd.1, Odd.2, no.1, no.2
O.F = overflow parameter selection :
Wh
, VAh –
INTG clears when 99999999
3D
AUTO
VA
VA.Fn
d.SEL
d.PAR
AUTO
VA
15
d.SEL
d.PAR
d.PRD
VA
15
9600
d.PAR
d.PRD
BAUD
Note: The PROG menu of EM 6433 and EM 6436 will not have “POLE” option
d.SEL, d.PAR, d.PRD are present only in meter with DM(Demand) option