ASCII I/F
CoolMasterNet PRM Rev 0.7
35
www.coolautomation.com
© 2017 CoolAutomation
>auto L2*
OK
Set all Indoor Units to auto mode
>auto
OK
haux
SYNOPSIS
haux [UID]
DESCRIPTION
Set ThermoPad(s), connected to CoolHub line, operation mode to haux.
EXAMPLE
Set ThermoPad 083 on line L3 to haux mode
>haux L3.083
OK
Set all ThermoPads on line L3 to haux mode
>haux L3
OK
Set all ThermoPads to haux mode
>haux
OK
temp
SYNOPSIS
temp [UID] [±]<TEMP>
temp [UID] <TEMP.d>
DESCRIPTION
Change Indoor Unit(s) Set Temperature.
· In form temp [UID] [±]<TEMP>
<TEMP> parameter must be decimal natural number. Command can work in relative or absolute manner. If plus
'+' or minus '-' sign precedes <TEMP> parameter it's value will be added to or substituted from current Set
Temperature value. Otherwise Set Temperature will be set to the given <TEMP> value.
· In form temp [UID\ <TEMP.d>
Set Temperature parameter <TEMP.d> is a fractal number with 0.1 precision. (In this case preceding +|- are not
allowed). If HVAC System does not support 0.1 precision for the Set Temperature (see table below), the final
value will be nearest supported value.
AC Type
Set Temperature
Precision
DK
0.1ºC
ME
0.1ºC
SM
0.1ºC
FJ
0.3ºC
SA
0.5ºC
TO
0.5ºC
PN
0.5ºC