ASCII I/F
CoolMasterNet PRM Rev 0.7
35
www.coolautomation.com
© 2017 CoolAutomation
>auto L2*
OK
Set all Indoor Units to auto mode
>auto
OK
haux
SYNOPSIS
haux [UID]
DESCRIPTION
Set ThermoPad(s), connected to CoolHub line, operation mode to haux.
EXAMPLE
Set ThermoPad 083 on line L3 to haux mode
>haux L3.083
OK
Set all ThermoPads on line L3 to haux mode
>haux L3
OK
Set all ThermoPads to haux mode
>haux
OK
temp
SYNOPSIS
temp [UID] [±]<TEMP>
temp [UID] <TEMP.d>
DESCRIPTION
Change Indoor Unit(s) Set Temperature.
· In form temp [UID] [±]<TEMP>
<TEMP> parameter must be decimal natural number. Command can work in relative or absolute manner. If plus
'+' or minus '-' sign precedes <TEMP> parameter it's value will be added to or substituted from current Set
Temperature value. Otherwise Set Temperature will be set to the given <TEMP> value.
· In form temp [UID\ <TEMP.d>
Set Temperature parameter <TEMP.d> is a fractal number with 0.1 precision. (In this case preceding +|- are not
allowed). If HVAC System does not support 0.1 precision for the Set Temperature (see table below), the final
value will be nearest supported value.