ASCII I/F
CoolMasterNet PRM Rev 0.7
38
www.coolautomation.com
© 2017 CoolAutomation
stat4 [UID]
DESCRIPTION
Get Indoor Unit(s) status list.
These commands are deprecated and are not recommended for use in CooMasterNet. They are implemented
for backward compatibility only. Detailed description of these commands can be found in the PRM of previous
CooMaster versions.
ls
SYNOPSIS
ls [UID]
DESCRIPTION
Get Indoor Unit(s) status list. If UID is omitted all Indoor Units connected to CoolMasterNet will be listed.
Indoor Unit status line has strict format, so that every status field is printed in fixed position.
· Indoor Unit status line with Celsius temperature scale
0123456789012345678901234567890123456
L2.102 OFF 20C 27C High Cool OK - 0
· Indoor Unit status line with Fahrenheit temperature scale
012345678901234567890123456789012345678
L2.102 OFF 120F 127F High Cool OK - 0
VLow, Low, Med, High, Top, Auto
Cool, Heat, Fan, Dry, Auto
OK - no failure, else Indoor Failure Code
EXAMPLE
>ls L2
L2.101 ON 25C 27C Low Cool OK - 1
L2.102 OFF 20C 27C High Cool OK - 0
OK
>ls L2.101
L2.101 ON 25C 27C Low Cool OK - 1
OK
>ls
L1.101 ON 25C 24C Low Cool OK - 1
L1.102 ON 22C 23C Med Cool OK - 0
L2.101 ON 25C 27C Low Cool OK - 1
L2.102 OFF 20C 27C High Cool OK - 0
OK