SYNOPSIS
ls2 [UID]
DESCRIPTION
Same as ls, but with decimal precision in temperatures.
Get Indoor Unit(s) status list. If UID is omitted all Indoor Units connected to CoolMasterNet will be listed.
Indoor Unit status line has strict format, so that every status field is printed in fixed position.
· Indoor Unit status line with Celsius temperature scale
01234567890123456789012345678901234567890
L1.102 ON 16.9C 27.0C High Cool OK - 0
· Indoor Unit status line with Fahrenheit temperature scale
0123456789012345678901234567890123456789012
L1.102 ON 062.4F 080.6F High Cool OK - 0
VLow, Low, Med, High, Top, Auto
Cool, Heat, Fan, Dry, Auto
OK - no failure, else Indoor Failure Code
EXAMPLE
>ls L2
L2.101 ON 25.7C 27.2C Low Cool OK - 1
L2.102 OFF 20.0C 27.3C High Cool OK - 0
OK
>ls L2.101
L2.101 ON 25.7C 27.2C Low Cool OK - 1
OK
>ls
L1.101 ON 25.4C 24.1C Low Cool OK - 1
L1.102 ON 22.1C 23.4C Med Cool OK - 0
L2.101 ON 25.7C 27.2C Low Cool OK - 1
L2.102 OFF 20.0C 27.3C High Cool OK - 0
OK
query
SYNOPSIS
query <UID_STRICT> <o|m|f|t|h|e|a|s>
DESCRIPTION
Query one of the operation conditions of given Indoor Unit. <UID_STRICT> parameter must define single Indoor