ASCII I/F
CoolMasterNet PRM Rev 0.7
40
www.coolautomation.com
© 2017 CoolAutomation
Unit in form Ln.XYY or XYY. Resulting value is printed as alpha-numeric value according to the table below.
Query
Operation Condition
Value
o
On/Off
0 - Off, 1 - On
m
Operation Mode
0 - Cool
1 - Heat
2 - Auto
3 - Dry
4 - Haux
5 - Fan
f
Fan Speed
0 - Low
1 - Medium
2 - High
3 - Auto
4 - Top
t
Set Temperature
Natural
e
Failure Code
0 - No failure, otherwise failure code
same as in ls command
a
Ambient Temperature
Natural
h
Set Temperature
0.01º Precision
s
Louver Position
0 - No Louver Control
a - auto (swing)
h - horizontal
3 - 30º
4 - 45º
6 - 60º
v - vertical
x - stop (swing)
EXAMPLE
>query L1.100 o
1
OK
>query L1.100 m
0
OK
>query L1.100 t
25
OK
>query L1.100 a
27
OK
>query L1.100 f
2
OK
>query L1.100 e
U4
OK
>query L1.100 e
0
OK
>query L1.100 h
20.50