ASCII I/F
CoolMasterNet PRM Rev 0.7
41
www.coolautomation.com
© 2017 CoolAutomation
OK
feed
SYNOPSIS
feed [UID] [±]<TEMP[.d]>
DESCRIPTION
This command defines CoolMasterNet Own Ambient Temperature (as if it were measured by CoolMasterNet
itself). Command can work in relative or absolute manner. If plus '+' or minus '-' sign precedes <TEMP>
parameter it's value will be added to or substituted from current value. Otherwise Own Ambient Temperature will
be set to the given <TEMP> value. <TEMP> can be provided with 0.1 precision. If <TEMP> is zero
CoolMasterNet will not use Own Ambient Temperature for it's operation.
CoolMasterNet keeps separate Own Ambient Temperature for each Indoor Unit.
Own Ambient Temp usage depends on HVAC Line type.
If not zero, sent to Indoor Unit as Smart Controller temperature sensor value
If not zero, sent to Indoor Unit as Wired Thermostat temperature sensor value
Temperature sent to Indoor Unit in i-feel message
EXAMPLE
Define Own Ambient Temperature to all Indoor Units on line L2
>feed L2 24.5
OK
Define Own Ambient Temperature to Indoor Unit 101 on line L1
>feed L1.101 27
OK
wh
SYNOPSIS
wh <UID_STRICT> <h|e|w|a|t<+|-|temp>|b<+|->>
wh <UID_STRICT>
DESCRIPTION
Control Water Heater Unit. When letter is omitted special water heater status is displayed.
Tank (+=on, -=off, temp=set point)