CX3G/FX3GC PLC Programming manual
www.coolmayplc.com
2
10KHz or double phase 2 -3channels up to 60KHz, and could be customized as single
phase 100khz or 2 channels double phase 60khz+ 1 channel 10khz; For FX3GC PLC,
regularly single phase 1 channels 100KHz4 channels 20KHz or double phase 1
channels 60KHz2 channels 10KHz
High speed pulse, regular as 8 channels Y0-Y3 in 100KHz,Y4-Y7 in 10KHz, could
be customized as 8 channels 10-100KHz;
Note: High speed counter+High speed pulse should be less 480KHz.
Support multiple types analog individually or mixed ones for analog output and
input.
Precision of AD/DA is 12bit.Temperature/current/voltage for input. current/voltage for
output.
For CX3G PLC, at most 16DI/8DO. For FX3GC-16M, com ports/ analog can be added,
at most 2 Rs485+1 CAN port+6AD/4DA can be added; or 1 Rs485+1 CAN
port+8AD/4DA can be added; or 1 RS485+8AD/6DA can be added or 2 RS485+ 1
CAN port can be added.
Up to 40DI/40DO for CX3G PLC, up to 16DI/16DO for FX3GC PLC.
Relay/transistor or mixed relay and transistor for output.
Convenient for wiring. CX3G adopts 5.00mm pluggable terminals. FX3GC adopts
3.5mm pluggable terminals.
Easy installation. DIN-Rail (35mm width) installation and fixed hole installation.
Flexible, can be customized accordingly.