Corning Optical Communications
Installation Manual
|
CMA-793-AEN
|
Page 26
It is necessary to allow at least 2 rack units (88 mm) of free space below each unit for heat dissipation without fan installed or 1 rack
unit (44 mm) of free space below each unit with fan occupied in the middle. Otherwise, the device temperature may rise and affect the
service life of the device.
4.
Reserve enough free space or Install the fan for cooling if multiple devices are installed in the same rack.