Wiring and Jumpers
April 2019CXX-UM-03060-EN-01Page 14
RM2
J2 J1
JMP-1
PGM PORT
EF4295 TERMINAL BLOCK LAYOUT
J5
J4
JMP-B
JMP-A
JMP-C
EC80 Flow Computer to PT02E-12-14P
EC80 B-9541 CABLE PT02E-12-14P
SCALING UNITS FUNCTION/SIGNAL J1 J4 J5 WIRE COLOR PINOUT
N/A
VDC+ PWR + 1 RED A
VDC- PWR RETURN 2 BLK B
N/A
N/A RS-485 + 5 WHT C
N/A RS-485 – 6 WHT/BLK D
N/A Hz RAW A OUT 1 ORG E
N/A Hz RAW B OUT 2 RED/WHT F
N/A Hz GND 3 ORG/BLK H
Hz FREQ 1 OUT 4 GRN J
Hz FREQ 2 OUT 5 GRN/WHT K
N/A Hz GND 6 GRN/BLK L
V ANALOG 1 VOLTAGE OUT 9 BLU M
V ANALOG 2 VOLTAGE OUT 8 BLU/WHT N
N/A N/A AGND 7 BLU/BLK P
N/A N/A ANALOG 4-20 mA RETURN – 3 RED/BLK P
mA ANALOG 4-20 mA OUT + 4 BLK/WHT R
Flow-Meter to EC80 Flow Computer
B-954 WIRE COLOR FUNCTION/SIGNAL J2 J5 PT02E-12-8P PINOUT
WHT RF PICKOFF A 1 A
WHT RF A RETURN 2 B
BLU RF PICKOFF B 3 C
BLU RF B RETURN 4 D
GRN RF PICKOFF Q 5 N/A
GRN RF Q RETURN 6 N/A
ORG RTD EX+ 4 E
ORG RTD + 3 F
ORG RTD – 2 G
ORG RTD EX- 1 H