6. Commissioning
6.1. Caution
6.1.1. Grounding:
The grounding of the chassis of UNIGEN must be done with the M5 screw. Use a 4mm² wire to connect to earth, this
cable should be as short as possible.
6.1.2. Wiring rules:
The cables with high voltage (400 VAC) and/or high current (5A) must be separated from the command cables. All the
command and digital inputs / outputs can be in the same cable path.
If you have to cross the command/DC cables with the 400V/5A cables, it is recommended to cross with a right angle.
The grounding must be done in a proper way to avoid personal injuries and for a reduction of EMC.
6.1.3. Vibrations:
In case of heavy vibrations, the UNIGEN should be mounted using AV Mounts.