EasyManua.ls Logo

CSZ ZPH 32 - Water Quality

Default Icon
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAINTENANCE WITH Q&A
Page 5-17
WATER QUALITY
Puri ed water is recommended for use with our humidity systems. Water
should be provided within 0.05 to 2M (.25 to 10ppm) DI and <2mg/L of
free chlorine, Distilled water or Reverse Osmosis (RO) water outside of
these limits may cause either corrosion or scaling. Tap water may be
used with our optional Demineralizer Filtration System. A Recirculation
Humidity Water Supply System is also available. Inlet water pressure
should not exceed 10psi for use with an atomizer or 25 psi for use with
a boiler. For optimal use of the atomizer and boiler systems, inlet water
pressure should not fall below 10 PSI (69 kPa) for both boilers and
atomizers. A Water Pressure Regulator must be used.
Water speci cation 0.05 to 2 Mega
OHMS in addition to <2mg/L of free
chlorine.
CAUTION
Failure to maintain cartridge may
result in chloride corrosion of
stainless steel interior surfaces
which is not covered under
warranty.
WARNING
!
!
Maximum water inlet pressure is
10 PSI (170 kPa) for an atomizer
and 25 PS (274 kPa)I for a boiler.
Exceeding this pressure may
cause catastrophic failure of the
lter housing. For optimal use of
the atomizer and boiler systems,
inlet water pressure should not
fall below 10 PSI (69 kPa) for both
boilers and atomizers.
WARNING
!

Table of Contents

Related product manuals