EasyManua.ls Logo

Cutler-Hammer Digitrip OPTIM 550 - 3-2.4 Long Delay Protection

Cutler-Hammer Digitrip OPTIM 550
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I.B. 29C891B
Page 26
Effective 11/98
Ground Fault
- Ground Fault Pickup
- Ground Fault Delay, Flat Response
- Ground Fault Delay, I
2
t Response
The ten curve shaping possibilities are illustrated in
Figure 3-5. Each portion of the curve is discussed and
illustrated individually in the following paragraphs (3-2.4,
3-2.5, 3-2.6 and 3-2.7).
Notice: For the sake of simplification, many curve illus-
trations in this section will be represented as
single line curves. Keep in mind, however, that
a time-current curve in reality is represented by
a band of minimum and maximum values, not
a single line (Figures 3-1 and 3-5).
3-2.4 LONG DELAY PROTECTION
All Digitrip OPTIM Trip Units provide programmable long
delay protection consisting of (Tables 3.2 and 3.3 and
Figure 3-4):
Long delay current setting
Long delay time setting
Long delay thermal memory
TIME
CURRENT
1
3
5
6
4A
7A
7B
4B
2B
2A
Note: Arrows indicate
direction of curve
movement
Figure 3-5 Typical OPTIM Trip Unit Time-Current Curve (10 Curve Shaping Adjustments)
OVERLOAD AND SHORT CIRCUIT
1. Long Delay Setting
2A. Long Delay Time I
2
t
2B. Long Delay Time I
4
t
SHORT CIRCUIT
3. Short Delay Pickup
4A. Short Delay Time Flat Response
4B. Short Delay Time I
2
t Response
5. Instantaneous
GROUND FAULT
6. Ground Fault Pickup
7A. Ground Fault Delay Flat Response
7B. Ground Fault Delay I
2
t Response
High load alarm (in software with IMPACC, and dis-
creet contact on R, SPB and DSII breakers)
Long Delay Current Setting (I
r
)
The long delay current setting (I
r
) is established as a
multiple of the rating plug value (I
n
). The programmable
range is as follows:
0.4 to 1.0 times (I
n
) in 0.01 increments
Example: A 600 ampere Series C L-Frame circuit break-
er with a 400 ampere rating plug installed and
the long delay current setting programmed to
160 amperes results in a 40% setting.
The long delay current setting (I
r
) for OPTIM Trip Units
is the nominal continuous current rating of the breaker.
The breaker will carry this maximum amount of current
(I
r
) continuously without tripping. It is not the actual
long delay pickup point. The breaker will pickup and
ultimately trip at a current level that is nominally higher
than the Long Delay Current Setting (I
r
):
For DSII/DSLII, Long Delay Pickup is calibrated for
nominally 105% (Ir)
For K, L, N and R-Frames and SPB, the calibration is
for nominally 116% (I
r
)

Table of Contents

Other manuals for Cutler-Hammer Digitrip OPTIM 550