ASY‑206‑077
9
6.3Automaticsynchronizationcontrol
6.3.1Incaseofsynchronizingclosingfrombus(receivingside)togenerator.
①Underthebusvoltageinputcondition(AC90to125V)andafterthegeneratorvoltageisstable(more
thanAC80V),automaticsynchronizationisdone.Underunstablevoltagecondition,thecontrolwillstop
anddisplayERROR(E5).(Willautomaticallyreturnwhenthevoltagecomesinwithintherange.)
②Whenvoltageandfrequencyarecontrolwithinthelimits(referto7pagesitem5.1),thedisplayof
phasedifferencedisplayLEDrotatesatthespeedaccordingtoafrequencydifference.
7segmentLEDofvoltage(△V)andfrequency(△F)displaysadifference.
③60R,60Loutputwillcontrolthedifferenceofbusandgeneratorvoltagewithinthesettingrange
(△V).LED△Vturnsonwithintherange.
④15R,15Loutputwillcontrolthedifferenceofbusandgeneratorvoltagewithinthesettingrange
(△F).LED△Fturnsonwithintherange.
⑤Incasethephasedifferenceisatsynchronizingpoint±15°underthesettingrangeinbothvoltage
andfrequencydifference,synchronismchecksignal(±15°)isoutputandLEDturnson.
⑥Circuitbreakerclosingsignal(25)willbeoutputaheadofsynchronizingpoint,accountingonthe
advancetimeofthecircuitbreakerclosingandLEDturnson,inordertoclosethecircuitbreaker
atsynchronizingpointunderthesettingrangeinbothvoltageandfrequencydifference.
Thecircuitbreakerinputsignal(25)isOFFafter+200msofadvancetime.(However,ifitcomesupto±
10°withinin200ms,itbecomesanOFF→inputmistake.)
6.3.2Incaseofsynchronizingclosingfromgeneratortobus(receiving).
①Automaticsynchronizationstartcanbedoneunderthebusvoltageinputcondition(AC90to125V)and
SLOWsideclosingdesignation(morethanAC80Vingeneratorvoltage)isinput.Thecontrolwillstop
underunstablevoltageconditioninthegeneratorsideandERROR(E5)isdisplayed.
(Willautomaticallyreturnatwhenitcomesinwithintherange.)
<Note>ReversepowerpreventionispossiblebySLOWsideclosingdesignation,inthereceivingside
atthetimeofsynchronizingclosing.)
②Whenvoltageandfrequencyarecontrolwithinthelimits(referto7pagesitem5.1),thedisplayof
phasedifferencedisplayLEDrotatesatthespeedaccordingtoafrequencydifference.
7segmentLEDofvoltage(△V)andfrequency(△F)displaysadifference.
③60R,60Loutputwillcontrolthedifferenceofbusandgeneratorvoltagewithinthesettingrange
(△V).LED△Vturnsonwithintherange.
④15R,15L
outputwillcontrolthedifferenceofbusandgeneratorvoltagewithinthesettingrange
(0〜‑△F).LED△Fturnsonwithintherange.
⑤Incasethephasedifferenceisatsynchronizingpoint±15°underthesettingrangeinbothvoltage
andfrequencydifference,synchronismchecksignal(±15°)isoutputandLEDturnson.
⑥Circuitbreakerclosingsignal(25)willbeoutputaheadofsynchronizingpoint,accountingonthe
advancetimeofthecircuitbreakerclosingandLEDturnson,inordertoclosethecircuitbreaker
atsynchronizingpointunderthesettingrangeinbothvoltageandfrequencydifference.
Thecircuitbreakerclosingsignal(25)turnsoffaftertheadvancetimeplus200ms.(Incaseof
closingfailure,itwillturnoffat±10°,whenitcomesupto±10°within200ms.)