EasyManua.ls Logo

Daiichi Electronics ASY-96 - Setting Example

Default Icon
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ASY‑206‑077
16
7.6Settingexample
7.6.1Settingitem
①Voltagedifference(△V)
②Frequencydifference(△F)
③Voltageadjustmentpulsewidth(Vpw)
④Voltageadjustmentpulseperiod(Vpint)
⑤Governorpulsewidth(Fpw)
⑥Circuitbreakeradvancetime(25T)
Settingitem Default Settingexample
Voltagedifference(△V) 5% 2%
Frequencydifference(△F) 0.1Hz 0.1Hz
Voltageadjustmentpulsewidth(Vpw) 0.5s 0.5s
Voltageadjustmentpulseperiod(Vpint) 2s 5s
Governorpulsewidth(Fpw) 0.5s 0.5s
Circuitbreakeradvancetime(25T) 50ms Range10〜310ms
7.6.2Judgmentofsettingpoint
★①Voltagedifference(AssumedΔV=2%atbusvoltage6600V)
Controlwithin±2%=±132V(6468to6732V)againstbusvoltage6600V.
★②Voltageadjustmentpulsewidth,pulseperiod(AssumedVpw=0.5s,Vpint=5s)
Voltagecontrolresolution(voltagechangeperpulse)willbe200V×0.5s/6s=16.7V/pulse,when
advancetimeis6s/200V.Thechangeis16.7Vforevery5s,becauseofthepulseperiodbeing5s.
★③Frequencydifference(Assumed△F=0.1Hz.)
Controlwithin0.1Hz=50Hz±0.1Hzagainstbusfrequency50Hz.
★④Governorpulsewidth(AssumedFpw=0.5s.)
Frequencycontrolresolution(frequencychangeperpulse)willbe1Hz×0.5/15s=0.033Hz/pulse.
Thechangeis0.033Hzforevery1/ΔF(s)becauseofthepulseperiodbeing1/ΔF.
★⑤Circuitbreakeradvancetime(25T)
10〜310msat△F=0.1Hz
10〜150msat△F=0.2HzThisisthesettingrange.
10〜80msat△F=0.3Hz
7.6.3Countermeasureincaseofunstablecontrolcondition.
1)Whenvoltagecontrolbecomeshunting.
①Increasevoltagedifference(△V).
②Decreasevoltageadjustmentpulsewidth(Vpw).
③Increasevoltageadjustmentpulseperiod(Vpint).
Changecanbedonebyoneoftheabovemeasuresortheircombinedmeasures.
2)Whenfrequencycontrolbecomeshunting.
①Increasefrequencydifference(△F).
②Decreasegovernorpulsewidth(Fpw).
Changecanbedonebyoneoftheabovemeasuresortheircombinedmeasures.
3)Whenvoltagecontroldelays.
①Increasevoltageadjustmentpulsewidth(Vpw).
②Decreasevoltageadjustmentpulseperiod(Vpint).
Changecanbedonebyoneoftheabovemeasuresortheircombinedmeasures.
4)Whenfrequencycontroldelays.
①Increasefrequencydifference(△F).
②Decreasegovernorpulsewidth(Fpw).
Changecanbedonebyoneoftheabovemeasuresortheircombinedmeasures.