ASY‑206‑077
18
7.8Errordisplayandtreatment
Contentsoferror
Control
status
Error
output
Resetcondition Note
E1 ROM/RAMerror Stop Alarm Equipmenttrouble
E2 A/Derror Stop Alarm Equipmenttrouble
E3 Settingerror Stop Automaticreturnbyreset
E4 Outofrange,busvoltage Stop Automaticreturn
E5 Outofrange,generatorvoltage Stop Automaticreturn
E6 Outofrange,busfrequency Stop Automaticreturn
E7 Outofrange,frequencydifference Stop Automaticreturn
E8
Startinputdesignationmistake.
(Overlappingdesignation)
Stop Automaticreturn
E9
Closingmistake.
(3timescontinuation)
Closing
outputstop
Alarm
Noinputvoltageorstart
OFF
ΔVandΔFcontrol
iscontinued
7.9Troubleshooting
Abnormalcondition Probablecause Treatment
Businputisnotgiven. Validationofbusinput.
1 POWERLEDisnotlighted.
Defectindevice Exchangeofdevice.
Outofcontrolrangeinvoltage/frequency
ofbusandgenerator.
Confirmofvoltageandfrequency
bybusandgenerator.
2
Figuresofvoltageand
frequencydifference
dontdisplay.
Defectindevice Exchangeofdevice.
Automaticinput(Automaticsynchronization
closingstart)isnotgiven.
Confirmofautomaticinput.
3
Automaticsynchronization
closingdontstart.
Defectindevice Exchangeofdevice.
Manualinput(Manualsynchronizationclosing
start)isnotgiven.
Confirmofmanualinput.
4
Manualsynchronization
closingdontstart.
Defectindevice. Exchangeofdevice.
E1:ROM/RAMerror
E2:A/Derror
Defectindevice,
Exchangeofdevice.
E3:Settingerror
Confirmofsettingvalue
(Correction).Settingchange
duringoperationisnotpossible.
E4:Outofrangeinbusvoltage.
E5:Outofrangeingeneratorvoltage.
Confirmofvoltagerange
E6:Outofrangeinbusfrequency.
E7:Outofrangeingeneratorfrequency.
Confirmoffrequencyrange.
E8:Errorinstartinputdesignation.
(Repetitiondesignation)
Confirmofstartinput
(Correction).
5
Errorisdisplayed.
(E1〜E9)
E9:Closingmistake.
(3timescontinuation)
Confirmofoutput(25)orcircuit
breaker.
AVRline,maybeinferiorif60R,60Lisoutput. ConfirmofAVRline.
6
Voltagedontbalance.
(△VLEDisnotlighted.)
Devicemaybedefectiveif60R,60Lisnot
output.
Exchangeofdevice.
Governorline,maybeinferiorif15R,15Lis
output.
Confirmofgovernor.
7
Frequencydontbalance.
(△FLEDisnotlighted.)
Devicemaybedefectiveif15R,15Lisnot
output.
Exchangeofdevice.
Closingconditionsarenotproper.
Confirmofclosingconditions
(△Vand△F).
8
Closingsignaldont
display(LED(25)isnot
lighted.)
Devicemaybedefective. Exchangeofdevice.
△Vand△Fisnotwithinrange. Confirm△Vand△F.
9
Synchronismchecksignal
dontdisplay(±15°LED
isnotlighted.)
Devicemaybedefective. Exchangeofdevice.
Synchronousclosing(25outputs)mistake
occursby3timescontinuation.
Confirmofcircuitbreakerline.
ROM/RAMerror.
10 Alarmisdisplayed.
A/Derror.
Exchangeofdevice.