ASY‑206‑077
7
5.Controlfunction
5.1Controlrange
Busvoltage:AC90〜125V
Generatorvoltage:Morethan80V
Busfrequency:50±3Hz,60±3Hz
Frequencydifference:Lessthan±4Hz
<Note>ControlwillstopatotherrangesthanaboveanddisplayERRORforeach.
5.2Controlsignalinput(1acontact,Switchingvoltage/currentDC12V,10mA)
(1)Automaticsynchronizationstartandmanualsynchronizationstart.
Startinput
Automatic
synchronization
Manual
synchronization
Output
ON OFF 60R/60L,15R/15L.Synchronismchecksignal(±15°),25.
OFF ON Synchronismchecksignal(±15°).
OFF OFF POWERLEDlights.
ON ON E8display(Overlapdesignation)
<Note>Underabovecondition,ONisterminalshort‑circuiting.OFFisterminaldisconnection.
(2)GeneratorSLOWsideclosingdesignation.
ON(Terminalshort‑circuit):ClosingfromSLOWside.(F
B
>F
G
)
OFF(Terminaldisconnection):Randomclosingdirection.(F
B
>F
G
orF
B
<F
G
)
5.3Controloutputandcontents
(1) Voltagebalancefunction(60R,60L)
Acontrolpulseisoutputtedinorderthatbusvoltage(V
B
)andgeneratorvoltage(V
G
)maybeputinto
regulationwithinthelimits.
(2) Advancingfunction(15R,15L)
Acontrolpulseisoutputtedinorderthatbusfrequency(F
B
)andgeneratorfrequency(F
G
)maybeput
intoregulationwithinthelimits.
(3) Withinfrequencydifferencesetting(ΔF).
Whenfrequencydifferencecontinuesover1second,withinsettingvalue(ΔF),ΔFLEDislighted.
Hysteresis0.03Hz(lightswithin0.1HzincaseofΔF=0.1Hz).
Return(LEDON→LEDOFF)willbeoverΔF+0.03Hz(LEDOFFat0.13HzincaseofΔF=0.1Hz).
(4) Withinvoltagedifferencesetting(ΔV).
Whenvoltagedifferencecomesinwithinsettingvalue(ΔV),ΔVLEDislighted.
Hysteresis0.5%(lightswithin4.5%incaseofΔV=5%)
Returnto5.0%ormore(LEDON→LEDOFF).
(5) Synchronismchecksignaling(±15°).
Whenvoltageandfrequencydifferencearewithinthesettingvalueandphasedifferencewithin±15°,
acontactsignalisoutputand±15°LEDturnson.
(6) Circuitbreakerclosingsignal(25).
Aftervoltageandfrequencydifferencecomesin
withinthesettingvalue,circuitbreakerclosing
signal(25)isoutputaheadofsynchronizing
point,accountingoncircuitbreakerclosing
advancetimeandLED(25)turnson.
Circuitbreakerclosingsignal(25)mustbeset
atOFFaftertheadvancetime+200ms.
Afteraclosingsignaloutput,incasethere
isnophaseshift(10°)for3seconds,it
becomesasynchronizingsuccess.
ItbecomesanENDdisplayandallcontrolis
stop.Incaseaphaseshift(10°)isin3
seconds,itbecomesasynchronizingclosing
failure.
200ms
25closingcommandOFF
(Atsynchronousclosingsuccess)
Advancetime
Synchronism
success
25closingcommandOFF
(Atsynchronousclosingmistake)
φ
Synchronous
closingmistake
25closing
output
25closing
command
10°