ASY‑206‑077
15
(6)Circuitbreakeradvancetimeissetting(5bitsdip‑switch).
SetatgivenvalueinreferencetoSWNo.Settable.Advancetimeisthesumattimethat“SW”is
“ON”condition.Thereisalimitintheadvancetimesetting,dependingonsettingoffrequency
difference(ΔF),incaseitissetatoutofthetimeofsettingrange.Thecontrolwillstopand
display“ERROR”(E3).
(Refertofollowsnote)
SW№ ON OFF Circuitbreakeradvancetimesettingvalue
1 10ms
2 20ms
Advancetimeisthesumofthetimethat“SW”is“ON”condition.
3 40ms
4 80ms
5 160ms
Advancetime=SW1+SW2+SW3+SW4+SW5
Settingattimeoffactorydelivery:50msunder“ON”conditionforSW1andSW3.
Factorysetting(SW1andSW3:ON,50mssetting)
SW№ ON OFF Circuitbreakeradvancetimesetting
1 〇 10ms
2 20ms
Advancetimeisthesumofthetimethat“SW”is“ON”condition.
3 〇 40ms
4 80ms
5 160ms
Advancetime=SW1+SW2+SW3+SW4+SW5
=10+0+40+0+0=50ms
<Note>Thereislimitinadvancetimesetting,dependingonfrequencydifferencesetting(ΔF).
Frequencydifference(ΔF) Setting
0.1Hz 10〜310ms
0.15Hz 10〜210ms
0.2Hz 10〜150ms
0.25Hz 10〜100ms
0.3Hz 10〜80ms
Incaseofsettingatoutofthetimeofthesettingrange,thecontrolwillstopanddisplay
“ERROR”(E3).