8 Faults and malfunctions
Installation and maintenance instructions
44
Daikin Altherma EHS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1444099_01 – 11/2018 – EN
Code Component/Designation Error Possible fault rectification
E198 FLS flow sensor,
3-way switch valve 3UVB1
Flow measurement not plausible Error occurs when 3UVB1 3-way switch valve is in
the bypass position, the internal circulation pump is
running but too low a volumetric flow is measured.
Required minimum water flow rate:
"Heating" operating mode: 600l/h
"Cooling" operating mode: 840l/h
Automatic thawing function active: 1020l/h
Air in heating system.
Vent.
Internal circulation pump is not running.
Check electrical connection and controller set-
tings. If the circulation pump is defective, re-
place it.
FLS flow sensor dirty, clogged.
Check, clean.
FLS flow sensor defective.
3UVB1 3-way switch valve drive defective.
Check, replace.
E200 Electrical components Communication fault Communication between the RoCon BM2C and
A1P printed circuit board lost.
Wiring or connections, poor contact.
Check, replace
E8005 Pressure sensor DS Water pressure in heating system too low Water pressure has fallen below permissible min-
imum value.
Insufficient water in the heating system.
Check the heating system for leaks, top up wa-
ter.
Pressure sensor DS defective.
Check, replace.
E8006 Pressure sensor DS Pressure drop in heating system too high Pressure drop too fast.
Check the heating system for leaks.
Pressure sensor DS defective.
Check, replace.
E8007 Pressure sensor DS Water pressure in heating system too high Water pressure has exceeded the permissible max-
imum value.
Too much water in the heating system.
Drain water.
Pressure sensor DS defective.
Check, replace.
E8100 Electrical components Communication Initialisation after heat pump start failed.
Printed circuit board A1P defective.
Check, replace.
E9000 Temporary internal message Not relevant for proper system operation.
E9001 Return flow temperature
sensor t
R2
Return flow temperature sensor error Sensor or connecting cable defective.
Check, replace.
E9002 Feed temperature sensor
t
V1
or t
V, BH
Inflow temperature sensor error Sensor or connecting cable defective.
Check, replace.
E9003 Frost protection function
fault
Plate heat exchanger (PWT) Measured value t
V1
<0°C
Failure of the frost protection function for the plate
heat exchanger because the water flow is too low.
See fault code E9004 / 7H.
Failure of the frost protection function for the plate
heat exchanger because there is a lack of refri-
gerant in the system. See fault code E9015 / E4.