8 Faults and malfunctions
Installation and maintenance instructions
45
Daikin Altherma EHS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1444099_01 – 11/2018 – EN
Code Component/Designation Error Possible fault rectification
E9004 FLS flow sensor Flow rate error Water flow is too low or non-existent.
Required minimum flow rate: see Chap. 5
Check the following items:
All stop valves of the water circuit must be com-
pletely open.
Optional water filters must not be contaminated.
Heating system must run within its operating
range.
Heating system and internal circulation pump
must be completely vented.
On the controller, check that sufficient water pres-
sure (>0.5bar) is available. [→Main menu →In-
formation → Overview →Psyst]
Check the function of the 3-way switching valve
3UVB1: Compare the actual position of 3UVB1
with the indicated position [→Main menu →In-
formation → Overview →BPV].
Does this fault occur during defrosting in room
heating or domestic hot water preparation operat-
ing mode? With optional backup heater: check its
power supply and fuses.
Check the fuses (pump fuse (FU1) on the A1P
printed circuit board and PCB fuse(F1) on the
RoCon BM2C printed circuit board).
Check the FLS flow sensor for soiling and func-
tion; clean, replace if necessary.
Frost damage on the plate heat exchanger (out-
door unit)
E9005 Inflow temperature sensor
t
V, BH
Inflow temperature t
V, BH
>75°C Feed temperature of backup heater (t
V, BH
) is too
high.
Inflow temperature sensor providing incorrect val-
ues. Temperature sensor or connecting cable de-
fective.
Check, replace.
Contact problem, A1P jumper on X3A.
E9006 Inflow temperature sensor
t
V, BH
Inflow temperature t
V, BH
>65°C
E9007 Circuit board A1P IG circuit board defective Communication between the heat pump outdoor
unit and heat pump indoor unit lost.
Electromagnetic influences.
Perform reset.
Printed circuit board A1P defective.
Replace A1P printed circuit board.
E9008 Temperature sensor (refri-
gerant fluid side) t
L2
Refrigerant temperature outside the valid range No heat consumption at the plate heat exchanger.
Check the flow rate.
If the flow rate is OK, replace the refrigerant tem-
perature sensor.
E9009 Optional: STB backup
heater (EKBUxx)
STB fault Thermal contactor (STB) in the backup heater (EK-
BUxx) has triggered.
Check and unlock the position of the STB.
E9010 Jumper on A1P circuit
board
Jumper missing on the "X21A" connection socket of
the A1P circuit board.
Install the jumper.
E9011 FLS flow sensor Flow sensor error FLS flow sensor defective.
Replace the FLS flow sensor.
E9012 Refrigerant temperature
sensor
Refrigerant temperature sensor error Measured value outside the permissible value
range. Sensor or connecting cable defective.
Check, replace.
E9013 Heat pump outdoor unit
main circuit board
AG circuit board defective
Main circuit board in the heat pump outdoor unit
defective.
Fan motor defective.
Check, replace.