8 Faults and malfunctions
Installation and maintenance instructions
46
Daikin Altherma EHS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1444099_01 – 11/2018 – EN
Code Component/Designation Error Possible fault rectification
E9014 High-pressure switch S1PH
in the refrigerant system
P
refrigerant
high Pressure in refrigerant system is too high.
High-pressure switch S1PH or fan motor defect-
ive.
Check, replace.
Poor wiring contact.
Flow rate in the heating system too low.
Filled refrigerant quantity too high.
Check, replace.
Service valves in the heat pump outdoor unit not
open.
Open the service valves.
E9015 Pressure sensor S1NPH in
the heat pump outdoor unit
P
refrigerant
low Pressure in refrigerant system too low.
Refrigerant quantity too low.
Check, eliminate cause, top up refrigerant.
Pressure sensor S1NPH in the heat pump out-
door unit defective.
Temperature sensor of fin heat exchanger R4T in
the heat pump outdoor unit defective.
Solenoid valve in the heat pump outdoor unit not
opening.
Main circuit board in the heat pump outdoor unit
defective.
Check, replace.
E9016 Electronic overload protec-
tion in the refrigerant com-
pressor
Compressor load protection Refrigerant compressor overload protection has
triggered. Pressure difference in the refrigerant cir-
cuit between high and low pressure side too high
(>26bar).
Refrigerant compressor defective.
Inverter circuit board in the heat pump outdoor
unit defective.
Refrigerant compressor/inverter circuit board wir-
ing, poor contact.
Filled refrigerant quantity too high.
Check, replace.
Service valves in the heat pump outdoor unit not
open.
Open the service valves.
E9017 Fan motor in the heat pump
outdoor unit
Ventilator blocked
A fan in the heat pump outdoor unit is blocked.
Check the fan for dirt or blockages; if neces-
sary, clean and free up.
Fan motor defective.
Fan motor wiring, poor contact.
Overvoltage at fan motor.
Fuse in the heat pump outdoor unit defective.
Inverter circuit board in the heat pump outdoor
unit defective.
Check, replace.
E9018 Electronic expansion valve Expansion valve The electronic expansion valve in the heat pump
outdoor unit is defective, replace.
E9019 Storage tank temperature
sensor t
DHW2
Hot water temperature >85°C The storage tank temperature sensor t
DHW2
delivers
a temperature value >85°C.
Sensor or connecting cable defective.
Check, replace.
E9020 Outlet temperature sensor
(hot gas sensor) R2T on
the heat pump outdoor unit
refrigerant compressor too
high
T
Evaporator
high
Outlet temperature sensor R2T on the refrigerant
compressor or connecting cable defective.
Refrigerant compressor defective.
Check, replace.