EasyManua.ls Logo

Daikin Altherma 3 H HT - To Connect the Power Consumption Digital Inputs

Daikin Altherma 3 H HT
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 | Electrical installation
Installer reference guide
114
EPRA14~18D + ETVZ16S18+23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
A
X1X2
LN
B
A
B
A4P
X2M
X1
a
X2
a Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
9.3.9 To connect the power consumption digital inputs
Wires: 2 (per input signal)×0.75mm²
Power limitation digital inputs: 12VDC / 12mA detection (voltage
supplied by PCB)
[9.9] Power consumption control.
1 Open the following (see "7.2.6To open the indoor unit"[460]):
1 Top panel
1
2
3
2 User interface panel
3 Upper switch box cover
2 Connect the power consumption digital inputs cable to the appropriate
terminals as shown in the illustration below.

Table of Contents

Other manuals for Daikin Altherma 3 H HT

Related product manuals