9 | Electrical installation
Installer reference guide
115
EPRA14~18D + ETVZ16S18+23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
A
1245
S6S
S7S
S8S
S9S
3
B
A
B
A8P
X801M
12345
a
a Installation of EKRP1AHTA is required.
3 Fix the cable with cable ties to the cable tie mountings.
9.3.10 To connect the safety thermostat (normally closed contact)
1 Open the following (see "7.2.6To open the indoor unit"[460]):
1 Top panel
1
2
3
2 User interface panel
3 Upper switch box cover
Main zone
Wires: 2×0.75mm²
2 Connect the safety thermostat (normally closed) cable to the appropriate
terminals as shown in the illustration below.