13 | Maintenance and service
Installer reference guide
229
EPRA14~18D + ETVZ16S18+23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
13.2.2 Yearly maintenance outdoor unit: instructions
Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt,
leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked heat
exchanger can lead to too low pressure or too high pressure leading to worse
performance.
Water filter
Close the valve. Clean and rinse the water filter.
NOTICE
Handle the filter with care. To prevent damage to the mesh of the filter, do NOT use
excessive force when you reinsert it.
1 3
2
13.2.3 Yearly maintenance indoor unit: overview
Water pressure
Water filters
Magnetic filter/dirt separator
Water pressure relief valve
Relief valve hose
Pressure relief valve of the domestic hot water tank
Switch box
Descaling
Chemical disinfection
13.2.4 Yearly maintenance indoor unit: instructions
Water pressure
Keep water pressure above 1bar. If it is lower, add water.
Water filters
Clean the water filters.
NOTICE
Handle the water filters with care. Do NOT use excessive force when you reinsert the
water filters so as NOT to damage the water filters mesh.

Table of Contents

Other manuals for Daikin Altherma 3 H HT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Altherma 3 H HT and is the answer not in the manual?

Daikin Altherma 3 H HT Specifications

General IconGeneral
TypeAir-to-water heat pump
Energy EfficiencyA+++
RefrigerantR-32
Max. Leaving Water Temperature70°C
Heating CapacityUp to 16 kW
Operating Temperature Range-25°C to 35°C
Sound Power LevelUp to 61 dB(A)

Related product manuals