10 | Configuration
Installer reference guide
159
EPRA14~18D + ETVZ16S18+23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
# Code Description
[2.D.1] [F-0B] The shut off valve:
▪ 0 No: is NOT influenced by heating or cooling
demand.
▪ 1 Yes: closes when there is NO heating or
cooling demand.
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room
thermostat request setting (NOT in case of leaving water temperature setting).
During cooling: If [F‑0B] is enabled, the shut off valve closes when the unit is
running in cooling operation mode. Enable this setting to avoid cold leaving water
through the heat emitter and the forming of condensation (e.g. under floor heating
loops or radiators).
# Code Description
[2.D.2] [F-0C] The shut off valve:
▪ 0 No: is NOT influenced by changing the space
operation mode to cooling.
▪ 1 Yes: closes when the space operation mode
is cooling.
WD curve type
The weather-dependent curve can be defined using the 2-points method or the
Slope-Offset method.
See "10.4.22-points curve"[4139] and "10.4.3Slope-offset curve"[4140].
# Code Description
[2.E] N/A ▪ 2-points
▪ Slope-Offset
10.5.4 Additional zone
Overview
The following items are listed in the submenu: