3/12
Breadcrumb Field code Setting name Range, step
Default valu
Date Value
Field settings table
Installer setting at variance with
default value
2.C.2 [8-06] R/W 0~10°C, step: 1°C
5°C
└─ Shut off valve
2.D.1 [F-0B] R/W
0: No
1: Yes
2.D.2 [F-0C] R/W 0: No
1: Yes
Main zone
2.E R/W 0: 2-points
1: Slo
Additional zone
3.4 0: Fixed
1: WD heating, fixed cooling(*3)
2: Weather de
└─ Heating WD curve
3.5 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
3.5 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
65°C
3.5 [0-02] R/W 10~25°C, step: 1°C
15°C
3.5 [0-03] R/W -40~5°C, step: 1°C
-15°C
└─ Cooling WD curve
3.6 [0-04] R/W [9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C(*3)
[2-0C]=1
7°C(*3)
[2-0C]=2
18°C(*3)
3.6 [0-05] R/W [9-07]~[9-08]°C, step: 1°C
22°C(*3)
3.6 [0-06] R/W 25~43°C, step: 1°C
35°C(*3)
3.6 [0-07] R/W 10~25°C, step: 1°C
20°C(*3)
Additional zone
3.7 [2-0D] R/O 0: Underfloor heating
1: Fancoil unit
2: Radiato
└─ Setpoint range
3.8.1 [9-05] R/W 15~37°C, step: 1°C
25°C
3.8.2 [9-06] R/W [2-0D]=2:
37~70, step: 1°C
70°C
[2-0D]≠2:
37~55, step: 1°C
55°C
3.8.3 [9-07] R/W 5~18°C, step: 1°C
7°C
3.8.4 [9-08] R/W 18~22°C, step: 1°C
22°C
Additional zone
3.A [C-06] R/W 0: -
1: 1 contact
2: 2 contacts
└─ Delta T
3.B.1 [1-0C] R/W 3~10°C, step: 1°C (*4)
3~12°C, step: 1°C (*5)
10°C
3.B.2 [1-0E] R/W 3~10°C, step: 1°C
5°C
Additional zone
3.C R/O 0: 2-points
1: Slo
Space heating / cooling
└─ Operation range
4.3.1 [4-02] R/W 14~35°C, step: 1°C
35°C
4.3.2 [F-01] R/W 10~35°C, step: 1°C
20°C
Space heating / cooling
4.4 [7-02] R/W 0: 1 LWT zone
1: 2 LWT zones
4.5 [F-0D] R/W 0: Continuous
1: Sample
2: Re
uest
4.6 [E-02] R/W (*3)
R/O
0: Reversible (*3)
1: Heatin
└─ Pump limitation
4.8.1 [9-0E] R/W 0~8, step:1
0 : No limitation
1~4 : 90~60% pump speed
5~8 : 90-60% pump speed during
sampling
6
4.8.2 [9-0D] R/W 0~8, step:1
0 : No limitation
1~4 : 90~60% pump speed
5~8 : 90-60% pump speed during
sampling
6
Space heating / cooling
4.9 [F-00] R/W
0: Restricted
1: Allowed
Pump outside range
Space cooling OFF temp
Number of zones
Pump operation mode
Unit type
Pump speed limitation main zone
Pump speed limitation additional zone
Cooling maximum
Thermostat type
Delta T heating
Delta T cooling
WD curve type
Space heating OFF temp
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Emitter type
Heating minimum
Heating maximum
Cooling minimum
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Max modulation
During thermo
During cooling
WD curve type
Setpoint mode
(*1) *6V*_(*2) *9W*_
(*3) Only applicable for models where cooling is possible_
(*4) E_(*5) E7
4P644735-1A - 2022.03