Daikin Altherma 3 H HT - Page 276

Daikin Altherma 3 H HT
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8/12
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with
default value
9.I [1-02] R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
9.I [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
9.I [1-04] R/W 0: Disabled
1: Enabled
9.I [1-05] R/W 0: Disabled
1: Enabled
9.I [1-06] R/W 10~25°C, step: 1°C
20°C(*3)
9.I [1-07] R/W
25~43°C, step: 1°C
35°C
(
*3
)
9.I [1-08] R/W [9-03]~[9-02]°C, step: 1°C
22°C(*3)
9.I [1-09] R/W [9-03]~[9-02]°C, step: 1°C
[2-0C]=0
18°C(*3)
[2-0C]=1
7°C(*3)
[2-0C]=2
18°C(*3)
9.I [1-0A] R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
9.I [1-0B] R/W 3~10°C, step: 1°C (*4)
3~12°C, step: 1°C (*5)
[2-0C] 2 (Radiator)
5°C
[2-0C] = 2 (Radiator)
10°C
9.I [1-0C] R/W 3~10°C, step: 1°C (*4)
3~12°C, step: 1°C (*5)
10°C
9.I [1-0D] R/W 3~10°C, step: 1°C
5°C(*3)
9.I [1-0E] R/W 3~10°C, step: 1°C
5°C(*3)
9.I [2-00] R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
9.I [2-01] R/W 0: No
1: Yes
9.I [2-02] R/W 0~23 hour, step: 1 hour
1
9.I [2-03] R/W
60°C
9.I [2-04] R/W 40~60 min, step: 5 min
40 min
9.I [2-05] R/W 4~16°C, step: 1°C
8°C(*3)
9.I [2-06] R/W 0: Disabled
1: Enabled
9.I [2-09] R/W -5~5°C, step: 0,5°C
0°C
9.I [2-0A] R/W -5~5°C, step: 0,5°C
0°C
9.I [2-0B] R/W -5~5°C, step: 0,5°C
0°C
9.I [2-0C] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I [2-0D] R/W 0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I [2-0E] R/W 20~50 A, step: 1 A
50 A
9.I [3-00] R/W 0: No
1: Yes
9.I [3-01]
0
9.I [3-02]
1
9.I [3-03]
4
9.I [3-04]
2
9.I [3-05]
1
9.I [3-06] R/W 18~30°C, step: 1°C
30°C
9.I [3-07] R/W 12~18°C, step: 1°C
12°C
9.I [3-08] R/W 25~35°C, step: 1°C
35°C
9.I [3-09] R/W 15~25°C, step: 1°C
15°C
9.I [3-0A] --
0
--
--
What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
What is the maximum desired room temperature in cooling?
What is the minimum desired room temperature in cooling?
What emitter type is connected to the additional LWT zone?
What is the maximum allowed current over the heatpump ?
Is auto restart of the unit allowed?
--
--
--
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
What emitter type is connected to the main LWT zone?
What is the desired delta T in cooling for the additional zone?
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
What is the disinfection target temperature?
How long must the tank temperature be maintained?
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
What is the averaging time for the outdoor temp?
What is the desired delta T in heating for the main zone?
What is the desired delta T in heating for the additional zone?
What is the desired delta T in cooling for the main zone?
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
Weather dependent cooling of the additional leaving water temperature zone
Low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
4P644735-1A - 2022.03
(*1) *6V*_(*2) *9W*_
(*3) Only applicable for models where cooling is possible_