6 | Application guidelines
Installer reference guide
36
EPRA14~18D + ETVZ16S18+23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
Setup
A Additional leaving water temperature zone
B Room 1
C Room 2
D Main leaving water temperature zone
E Room 3
a Heatpump convectors (+ controllers)
b Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
▪ For the main zone: the room temperature is controlled by the dedicated Human
Comfort Interface (BRC1HHDA used as room thermostat).
▪ For the additional zone:
- The external thermostat is directly connected to the indoor unit.
- The desired room temperature is set via the external thermostat and the
thermostatic valves of the radiators in each room.
- The heating demand signal from the external thermostat is connected to the
digital input on the indoor unit (X2M/35a and X2M/30). The indoor unit will
only supply the desired additional leaving water temperature when there is an
actual demand.
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
2 (Room thermostat): Unit operation
is decided based on the ambient
temperature of the dedicated Human
Comfort Interface.
Note:
▪ Main room = dedicated Human
Comfort Interface used as room
thermostat functionality
▪ Other rooms = external room
thermostat functionality
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
1 (Dual zone): Main + additional