9 | Electrical installation
Installer reference guide
98
EPRA14~18D + ETVZ16S18+23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
L1 L2 L3 N PE
b
a
L1
L2
L3
N
3N~,
50 Hz,
400 V AC
b
a
Q1DI
L1
L2
L3
N
F1B
1
3
5
7
2
4
6
8
IIII
BRN
GRY
BLK
BLU
YLW/GRN
a Power supply cable (field supply)
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse: 4 pole, 16A or 20A fuse, C
curve.
Q1DI Earth leakage circuit breaker (30mA)(field supply)
2 Interconnection cable (indoor↔outdoor):
Route the cable through the frame.
Connect the wires to the terminal block (make sure the numbers match with
the numbers on the indoor unit) and the earth screw.
Fix the cable with a cable tie.
Wires: (3+GND)×1.5mm²