9 | Electrical installation
Installer reference guide
104
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
4 (Optional) Power saving function: If you want to use the power saving
function:
▪ Disconnect X804A from X805A.
▪ Connect X804A to X806A.
INFORMATION
Power saving function. The power saving function is only applicable for V3 models.
For more information about the power saving function ([9.F] or overview field setting
[E‑08]), see "Power saving function"[4216].
In case of W1 models
1 Power supply cable:
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block.
▪ Fix the cable with a cable tie.
Wires: 3N+GND
Maximum running current: Refer to name plate on unit.
—