6 | Application guidelines
Installer reference guide
50
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
0
–30 –25 –20 –15 –10 –5 0 5
20
30
40
50
60
10
T
a
(°C)
T
min
(°C)
T
a
Outdoor temperature
T
min
Minimum weather-dependent setpoint for auxiliary gas boiler
6.4 Setting up the domestic hot water tank
6.4.1 System layout – Standalone DHW tank
a DHW tank
b Cold water IN
c Hot water OUT
d Motorised 3‑way valve
6.4.2 Selecting the volume and desired temperature for the DHW tank
People experience water as hot when its temperature is 40°C. Therefore, the DHW
consumption is always expressed as equivalent hot water volume at 40°C.
However, you can set the DHW tank temperature at a higher temperature
(example: 53°C), which is then mixed with cold water (example: 15°C).
Selecting the volume and desired temperature for the DHW tank consists of:
1 Determining the DHW consumption (equivalent hot water volume at 40°C).
2 Determining the volume and desired temperature for the DHW tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent
hot water volume at 40°C) using typical water volumes: