7 | Unit installation
Installer reference guide
68
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
c
a
b
c
d
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
In any case, provide at least 150 mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100 mm above the maximum expected
level of snow. See "7.3Mounting the outdoor unit"[473] for more details.
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.
7.1.3 Installation site requirements of the indoor unit
INFORMATION
Also read the precautions and requirements in the "2 General safety
precautions"[410].
The indoor unit is designed for indoor installation only and for the following
ambient temperatures:
- Space heating operation: 5~30°C
- Space cooling operation: 5~35°C
- Domestic hot water production: 5~35°C
INFORMATION
Cooling is only applicable in case of reversible models.
Mind the measurement guidelines:
Maximum height difference between indoor unit and outdoor
unit
10m
Maximum height difference between domestic hot water tank
and outdoor unit
10m
Maximum water piping length between indoor unit and
domestic hot water tank
10m
Maximum distance between the 3‑way valve and the indoor
unit (for installations with domestic hot water tank)
3m