3 | Specific installer safety instructions
Installer reference guide
17
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
Opening and closing the units (see
"7.2Opening and closing the units"[
4
69]
)
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
Piping installation (see
"8Piping installation"[
4
83]
)
WARNING
Field piping method MUST be in accordance with the instructions from this manual.
See "8Piping installation"[483].
WARNING
Install the tundish away from any electrical device. Possible consequence: Electrical
shock or fire.
In case of freeze protection by glycol:
WARNING
Due to the presence of glycol, corrosion of the system is possible. Uninhibited glycol
will turn acidic under the influence of oxygen. This process is accelerated by the
presence of copper and high temperatures. The acidic uninhibited glycol attacks
metal surfaces and forms galvanic corrosion cells that cause severe damage to the
system. Therefore it is important that:
▪ the water treatment is correctly executed by a qualified water specialist,
▪ a glycol with corrosion inhibitors is selected to counteract acids formed by the
oxidation of glycols,
▪ no automotive glycol is used because their corrosion inhibitors have a limited
lifetime and contain silicates which can foul or plug the system,
▪ galvanized pipes are NOT used in glycol systems since the presence may lead to
the precipitation of certain components in the glycol's corrosion inhibitor.
WARNING
Ethylene glycol is toxic.
Electrical installation (see
"9Electrical installation"[
4
96]
)
DANGER: RISK OF ELECTROCUTION