10 | Configuration
Installer reference guide
182
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
# Code Description
[5.6] [6-0D] Heat up mode:
▪ 0: Reheat only: Only reheat operation is
allowed.
▪ 1: Schedule + reheat: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
▪ 2: Schedule only: The domestic hot water
tank can ONLY be heated according to a
schedule.
See the operation manual for more details.
INFORMATION
Risk of space heating capacity shortage for domestic hot water tank without internal
booster heater: In case of frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when selecting the following:
Tank > Heat up mode > Reheat only.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
# Code Description
[5.7.1] [2‑01] Activation:
▪ 0: No
▪ 1: Yes
[5.7.2] [2‑00] Operation day:
▪ 0: Every day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5: Friday
▪ 6: Saturday
▪ 7: Sunday
[5.7.3] [2‑02] Start time
[5.7.4] [2‑03] Tank setpoint:
55°C~75°C
[5.7.5] [2‑04] Duration:
5~60minutes