15 | Disposal
Installer reference guide
263
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
Components
To activate/deactivate the recovery mode, you need the following components:
X1 7‑LEDs display
BS1~BS3 Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
To activate the recovery mode
INFORMATION
If you get confused in the middle of the process, press BS1 to return to the default
situation.
Before recovering refrigerant, activate the recovery mode as follows:
# Action 7-LEDs display
(a)
H1P H2P H3P H4P H5P H6P H7P
1 Start from the default situation.
2 Press and hold BS1 for 5seconds.
3 Press BS2 9times.
4 Press BS3 once.
5 Press BS2 once.
6 Press BS3 once.
7 Press BS3 once.
The flashing H1P indicates the
recovery mode has been correctly
selected and is activated.
8 Press BS1 once.
H1P keeps flashing, indicating that
you are in a mode that does not
allow compressor operation.
(a)
= OFF, = ON, and = flashing.
Result: The recovery mode is activated. The unit opens the electronic expansion
valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows: