10 | Configuration
Installer reference guide
137
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
# Code Description
[A.2.1.9] [F-0D] When the space heating/cooling control is OFF by
the user interface, the pump is always OFF,
unless pump operation is required due to safety
precautions. When the space heating/cooling
control is On, you can select the desired pump
operation mode (only applicable during space
heating/cooling)
Pump operation mode:
0 (Continuous): Continuous pump operation,
regardless of thermo ON or OFF condition.
Remark: continuous pump operation requires
more energy than sample or request pump
operation.
a
b c
d
b c
- a: Space heating/cooling control (user
interface)
- b: OFF
- c: On
- d: Pump operation
continued >>