12 | Commissioning
Installer reference guide
200
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
1 Set the user permission level to Installer. See "To set the user permission level
to Installer"[4131].
2 Go to [A.7.1]: > Installer settings > Commissioning > Test run.
3 Select a test and press . Example: Heating.
4 Select OK and press .
Result: The test run starts. It stops automatically when done (±30min). To stop it
manually, press , select OK and press .
INFORMATION
If 2 user interfaces are present, you can start a test run from both user interfaces.
The user interface used to start the test run displays a status screen.
The other user interface displays a "busy" screen. You cannot use the user
interface as long as the "busy" screen is shown.
If the installation of the unit has been done correctly, the unit will start up during
test operation in the selected operation mode. During the test mode, the correct
operation of the unit can be checked by monitoring leaving water temperature
(heating/cooling mode) and tank temperature (domestic hot water mode).
To monitor the temperature, go to [A.6] and select the information you want to
check.
During a heating test run, the unit will start up in hybrid operation. The setpoint of
the gas boiler during a heating test run is 40°C. Keep in mind the 5°C overshoot
that is possible during boiler operation, especially in combination with floor heating
loops.
12.4.4 To perform an actuator test run
Perform an actuator test run to confirm the operation of the different actuators.
For example, when you select Pump, a test run of the pump will start.
Purpose of the actuator test run is to confirm the operation of the different
actuators (e.g., when you select pump operation, a test run of the pump will start).
Prerequisite: Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user permission level
to Installer"[4131].
2 Make sure the room temperature control, the leaving water temperature
control and the domestic hot water control are turned OFF via the user
interface.
3 Go to [A.7.4]: > Installer settings > Commissioning > Actuator
test run.
4 Select an actuator and press . Example: Pump.
5 Select OK and press .
Result: The actuator test run starts. It automatically stops when finished. To stop it
manually, press , select OK and press .
Possible actuator test runs
Pump test