4 | Specific installer safety instructions
Installer reference guide
23
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
CAUTION
Sealing rings should ONLY be moisturized with water before use. Do NOT use
soap or other detergents.
When installing flues in voids, make sure that they are connected and fixed
correctly. If in an existing situation a visual inspection is NOT possible, the boiler
must NOT be commissioned and remain disconnected from the gas supply until
suitable access has been realised.
Make sure to follow the manufacturer’s instructions regarding maximum length
of the flue system, the appropriate flue material, correct jointing methods and
the maximum distance between flue support.
Make sure that all joints and seams are gastight and watertight.
Make sure that the flue system has a uniform gradient back to the boiler.
WARNING
Flue materials of different markings must NOT be combined.
CAUTION
These regulations are typical for both concentric and parallel flue systems.
The flue system MUST be secured to a solid structure.
The flue system should have a continuous fall back to the boiler (1.5°~3°). Wall
terminals MUST be installed levelled.
Only use accompanying brackets.
Every elbow MUST be secured by using the bracket. Exception at connecting on
boiler: if the length of the pipes before and after the first elbow is ≤250mm, the
second element after the first elbow has to contain a bracket. The bracket MUST
be positioned on the elbow.
Every extension MUST be secured per meter with a bracket. This bracket MUST
not be clamped around the pipe ensuring free movement of the pipe.
Make sure that the bracket is locked into the correct position depending on the
position of the bracket on the pipe or elbow.
Do NOT mix flue parts or clamps of different suppliers.
Piping installation (see
"8Piping installation"[
4
84]
)
WARNING
The field piping method MUST be in accordance with the instructions from this
manual. See "8Piping installation"[484].
DANGER: RISK OF BURNING/SCALDING
NOTICE
Do NOT use mineral oil on flared part.
Do NOT reuse piping from previous installations.
NEVER install a drier to this R410A unit to guarantee its lifetime. The drying
material may dissolve and damage the system.