ESIE09-08B Troubleshooting by Indication on the Remote Controller
Troubleshooting 147
3.14 “E3 Outdoor Unit: Actuation of High Pressure Switch
Remote Control
Display
E3
Subcode 1
Applicable
Models
ER*Q 011~016*
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure: 3.0MPa
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of High pressure switch
Defect of outdoor unit PC board (A1P)
Instantaneous power failure
Faulty high pressure sensor