Troubleshooting by Indication on the Remote Controller ESIE09-08B
200 Troubleshooting
3.56 “U4 ” Malfunction of Transmission between Indoor Unit
and Outdoor Unit
Remote Control
Display
U4
U4
subcode 0
Applicable
Models
AII indoor unit models
ER*Q 011~016*
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor and outdoor unit is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor transmission wiring F1, F2 disconnection, short circuit or wrong wiring
Outdoor unit power supply is OFF
Defect of outdoor unit PC board
Defect of indoor unit PC board (A1P)