ESIE09-08B Troubleshooting by Indication on the Remote Controller
Troubleshooting 211
[CHECK 3] Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector on motor side disconnected, measure the resistance between
each pin, then make sure that the resis
tance is more than the value mentioned in the
following table.
Measurement point Judgment
1 - 4 1M or more
2 - 4 100k or more
3 - 4 100 or more
4 - 7 100k or more
GND
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red