EasyManua.ls Logo

Daikin Altherma HT - Page 283

Daikin Altherma HT
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE09-08B Precautions for New Refrigerant (R-410A)
Precautions for New Refrigerant (R-410A) 271
1. Flaring tool
Specifications
Dimension A
Differences
Change of dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
cond
itioners, perform pipe flaring with a pipe extension margin
of
1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
Flare gauge
Nominal size
1/4
3/8
1/2
5/8
3/4
Tube O.D.
Do
6.35
9.52
12.70
15.88
19.05
Class-2 (R-410A)
9.1
13.2
16.6
19.7
24.0
Class-1 (Conventional)
9.0
13.0
16.2
19.4
23.3
+0
-0.4
Unit:mm
A
Dimension A
For class-1: R-407C
For class-2: R-410A

Table of Contents

Other manuals for Daikin Altherma HT

Related product manuals