Field Setting ESIE09-08B
82 Test Operation
7 Option setup
00 Optional bottom plate heater installed 0
(OFF
)
0/1
01 Not applicable. Do not change the default
valu
e.
0
(OFF)
0/1
02 Multiple set point pattern 0 (A) 0/1
03 Multiple set point 1 0
(OFF
)
0/1
04 Multiple set point 2 0
(OFF
)
0/1
8 Option setup
00 Remote controller temperature control 1 (ON) 0/1
01 Status: automatic restart function 1 (ON) 0/1
02 Emergency mode 0
(OFF
)
0/1
03 Status: low noise level 1 1~3 1
04 Status: freeze up prevention 0 0~2 1
9 Automatic temperature compensation
00 Leaving water temperature compensation
valu
e
0 –5~5 0.5 °C
01 Domestic hot water tank compensation
valu
e
0 –5~5 0.5 °C
02 Thermo ON/OFF admission 0 –5~5 0.5 °C
A Option setup
00 Not applicable. Do not change the default
valu
e.
0 0~2 1
01 Not applicable. Do not change the default
valu
e.
0 0~2 1
02 Set point: required temperature difference
for lea
ving and returning water
10 5~15 1 °C
03 Set point: multiple set point 1 required
temper
ature value
35 25~80 1 °C
04 Set point: multiple set point 2 required
temper
ature value
65 25~80 1 °C
B Domestic hot water set points
00 Set point: reheat minimum temperature 35 35~65 1 °C
01 Set point: reheat maximum temperature 45 35~75 1 °C
02 Status: weather dependent domestic water
heating
1 (ON) 0/1
03 Set point: storage temperature 70 45~75 1
°C
First
code
Second
code Setting name
Installer setting at variance with
default value
Default
value Range Step UnitDate Value Date Value