ESIE09-08B Field Setting
Test Operation 87
3.1.3 Detailed Explanation of Setting Modes
[0] Remote control setup
[0-00] User permission level
The remote controller can be programmed to make certain buttons and functions
unavailable for the user. There are 2 permission levels de
fined. Both levels (level 2 and
level 3) are basically the same, the only difference is that for level 3 no water temperature
settings are possi
ble (see table below).
By default no level is defined so all buttons and functions are operable (no level enabled).
The actual permission level is determined by field setting. For permiss
ion level 2, set field
setting [0-00] is to 2, for permission level 3, set field setting [0-00] to 3.
Once the field setting is set, the chosen permission level is not yet active. Enabling the
selected permiss
ion level is done by simultaneously press
ing buttons pi and pj
immediately followed by simultaneously pressing buttons s and ba, and keeping all 4
buttons pressed for at least 5 seconds. Note that no indication on the remote controller is
given. After the procedure the blocked buttons will not be available anymore.
Deactivating the selected permission level is done on the same way. Here the default level
becomes
a
ctive again. All buttons and functions are operable.
[0-01] Room temperature compensation value
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This
can be used as counte
rmeasure
for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus compensation value) is
then
used for controlling the system and will be displayed in the temperature read-out mode. See
also "[9] Automatic temperature compensation" setting for compensation values for leaving
water temperature and domestic hot water temperature.
[0-03] Status: defines whethe
r the ON/OFF instruction can be used i
n
the schedule
timer for space heating.
The schedule timer for space heating can be programmed on 2 differe
nt ways: based on the
temperature set point (both leaving water temperature and room temperature) and based on
the ON/OFF instruction.
First
code
Second
code Setting name
Default
value Range Step Unit
0 Remote control setup
00 User permission level 2 2~3 1 —
01 Room temperature compensation value 0 –5~5 0.5 °C
03 Status: space heating schedule timer mode 1 (ON) 0/1 — —
Permission
level 2 level 3
Operation ON/OFF Operable Operable
Domestic water heating operation ON/OFF Operable Operable
Setting the leaving water temperature Operable —
Setting the room temperature Operable Operable
Quiet mode ON/OFF — —
Weather dependent set point operation ON/OFF Operable —
Setting the clock — —
Programming the schedule timer — —
Schedule timer operation ON/OFF Operable Operable
Field settings — —
Error code display Operable Operable
Test operation — —