Installer reference guide BRC1E53
17
4P419250-1 – 2015.10
Field settings
Mode
No.
(Note
1)
FIRST
CODE
NO.
Description of the setting
SECOND CODE NO. (Note 2)
01 02 03 04
10 (20)
0
Filter Contamination -
Heavy/Light Setting for
when "Time to clean the
air lter" icon is shown
(when lter contamination
is heavy the time to clean
the air lter is to be
halved).
Ultra long
life lter
Light
±10.000 hrs.
Heavy
±5.000 hrs.
— —
Long life
lter
±2.500 hrs. ± 1.250 hrs.
Standard
lter
±200 hrs. ± 100 hrs.
1
Long-life lter type (setting of the lter
sign indication time).
(Change setting when a ultra-long
lter is installed).
Long-life lter
Ultra-long life
lter
— —
2
Thermostat sensor in the remote
controller.
Use combined
(with indoor
thermistor)
Do not use
Use
exclusively
—
3
Setting for when the lter sign is not to
be displayed.
Display Do not display — —
11 (21) 0
Number of connected SkyAir
simultaneous operation indoor units
(setting for simultaneous operation
system).
Pair Twin Triple
Double
twin
12 (22)
1
External On/Off input from outside
(setting for when forced On/Off is to
be operated from somewhere else).
Forced OFF
On/Off
operation
Emergency
Forced
OFF
2
Thermostat differential changeover
(setting for when using a remote
sensor).
1°C 0.5°C — —
13 (23)
0
High air outlet velocity (for high ceiling
applications).
h ≤ 2.7 m
2.7 m < h
≤ 3.0 m
3.0 m < h
≤ 3.5 m
—
1
Selection of airow direction (setting
for when a kit has been installed that
blocks the airow).
4-way ow 3-way ow 2-way ow —
3
Selection of airow function (setting
for when using a decoration panel at
the outlet).
Equipped Not equipped — —
4 Airow direction range setting. Upper Normal Lower —
6
The external static pressure setting
(setting according to the connected
duct resistance).
Normal
High static
pressure
Low static
pressure
—
FHYK: follow the high ceiling setting. Normal High ceiling — —
15 (25) 3
Drain pump operation with
humidifying.
Equipped Not equipped — —
1c 1
Thermostat sensor used for the "Auto"
operation mode and the Setback
function (room temperature on
detailed display).
Indoor thermistor
(intake
temperature)
Remote
controller
thermistor
— —
1c 12 External input B1. Do not use Use — —
1c 13 External input B2. Do not use Use — —
1e 2 Setback function. Do not use Heat only Cool only
Cool and
Heat
1e 7 Rotation overlap time. 30 minutes 15 minutes 10 minutes 5 minutes