GAS SUPPLY PIPING
WARNING
WARNING
gas and gas input rating. Make sure the unit is equipped
authorized conversion kit (see the unit Technical Manual for
latest edition of the National Fuel Gas Code NFPA 54/ANSI
Z223.1 or National Standard of Canada, Natural Gas and
Propane Installation Code, CSA B149.1.
NATURAL Min. 5.0" W.C., Max. 10.0" W.C.
PROPANE Min. 11.0" W.C., Max. 13.0" W.C.
INLET GAS PRESSURE
The minimum supply pressure should not vary from that
premature heat exchanger failure.
National Fuel Gas Code NFPA 54 / ANSI Z223.1.
Pressure= .50 PSIG or less and Pressure Drop of 0.3" W.C.
(Based on 0.60 Specific Gravity Gas)
Natural Gas Capacity of Pipe
in Cubic Feet of Gas Per Hour (CFH)
Nominal Black Pipe Size (inches)
Heating Value of Gas (BTU/Cubic Foot
1.
codes.
2.
fuel used.
3.
4.
of three inches long.
5.
the gas valve to keep it from turning.
6.
7.
8.
•
•
exterior locations).