EasyManua.ls Logo

Daikin DHG - Start-Up Procedure and Checklist

Daikin DHG
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24






evacuate excess concentration. If a Zone Control system


Accessory PCB to ensure that the Zoning Dampers open
during mitigation mode to provide ventilation throughout


information concerning mitigation mode. Once sensors


resume its normal operation. If the sensors detect another


WARNING







NOTE: 














NOTE:   


Single Stage Cooling Application: Refer to the Design

Two-Stage Cooling Application: 

1. Purge gauge lines. Connect service gauge manifold


2. Temporarily install thermometer on liquid (small) line


3.      
      
      

        

NOTE: To adjust superheat, turn the valve stem
clockwise to increase and counterclockwise to
decrease. Refer to TXV Superheat Adjustment
referenced in this manual.
         

       

         


NOTE: Do NOT adjust the charge based on
suction pressure unless there is a gross
undercharge. If an under charge is suspected,
recover the charge, re-evacuate the system,
and recharge per data plate. No adjustments
should be made if suspecting a charge issue.
4. Disconnect manifold set, installation is complete.
DHG036 15-17 2-4 TXV Low 82
DHG048 16-17 2-4 TXV Low 82
DHG060 14-17 5-7 TXV Low 82
DHG072 14-18 7-11 TXV Low 82
Design Superheat & Subcooling
Mode l
Superheat
(°F)
Subcooling
(°F)
Expansion
Device
Cooling
Stage
Outdoor
Ambient

󰀨
1. 


Test/Balance Menu to force the unit to OFF MODE.
2. Inspect all registers and set them to the normal open
position.
3. Turn on the electrical supply at the disconnect.
4. 

DDC controls installed, use Test/Balance Menu to

internal delays.
5. 

DDC controls installed, use Test/Balance Menu to

internal delays.

Related product manuals