EasyManua.ls Logo

Daikin EBLA16D V3 - Page 22

Daikin EBLA16D V3
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Electrical installation
Installation manual
22
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620239-1B – 2022.05
Item Description
Room thermostat
(wired or wireless)
In case of wireless room
thermostat, see:
Installation manual of the wireless
room thermostat
Addendum book for optional
equipment
In case of wired room thermostat
without multi-zoning base unit, see:
Installation manual of the wired
room thermostat
Addendum book for optional
equipment
In case of wired room thermostat
with multi-zoning base unit, see:
Installation manual of the wired
room thermostat (digital or
analogue) + multi-zoning base unit
Addendum book for optional
equipment
In this case:
You need to connect the wired
room thermostat (digital or
analogue) to the multi-zoning
base unit
You need to connect the multi-
zoning base unit to the outdoor
unit
For cooling/heating operation,
you also need to implement a
relay (field supply, see
addendum book for optional
equipment)
Wires: 0.75mm²
Maximum running current: 100mA
For the main zone:
[2.9] Control
[2.A] Ext thermostat type
For the additional zone:
[3.A] Ext thermostat type
[3.9] (read-only) Control
Item Description
Heat pump convector There are different controllers and
setups possible for the heat pump
convectors.
Depending on the setup, you also
need to implement a relay (field
supply, see addendum book for
optional equipment).
For more information, see:
Installation manual of the heat
pump convectors
Installation manual of the heat
pump convector options
Addendum book for optional
equipment
Wires: 0.75mm²
Maximum running current: 100mA
For the main zone:
[2.9] Control
[2.A] Ext thermostat type
For the additional zone:
[3.A] Ext thermostat type
[3.9] (read-only) Control
Remote outdoor
sensor
See:
Installation manual of the remote
outdoor sensor
Addendum book for optional
equipment
Wires: 2×0.75mm²
[9.B.1]=1 (External sensor =
Outdoor)
[9.B.2] Ext. amb. sensor offset
[9.B.3] Averaging time
Remote indoor sensor See:
Installation manual of the remote
indoor sensor
Addendum book for optional
equipment
Wires: 2×0.75mm²
[9.B.1]=2 (External sensor = Room)
[1.7] Room sensor offset
Human Comfort
Interface
See:
Installation and operation manual of
the Human Comfort Interface
Addendum book for optional
equipment
Wires: 2×(0.75~1.25mm²)
Maximum length: 500m
[2.9] Control
[1.6] Room sensor offset

Table of Contents

Related product manuals