EasyManua.ls Logo

Daikin ERLA03DAV3 - 2-Points Curve; Using Weather-Dependent Curves

Daikin ERLA03DAV3
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 | Configuration
Installer reference guide
128
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
INFORMATION
To operate weather dependent, correctly configure the setpoint of the main zone,
additional zone or tank. See "10.3.3Using weather-dependent curves"[4128].
10.3.2 2-points curve
Define the weather-dependent curve with these 2 setpoints:
▪ Setpoint (X1, Y2)
▪ Setpoint (X2, Y1)
Example
Set weather-dependent heating
Confirm
Adjust
Scroll
T
t
T
a
X1
Y1
Y2
X2
X1, X2 Examples of outdoor ambient temperature
Y1, Y2 Examples of desired tank temperature or leaving water temperature
10.3.3 Using weather-dependent curves
Configure weather-dependent curves as following:
To define the setpoint mode
To use the weather-dependent curve, you need to define the correct setpoint
mode:
Go to setpoint mode … Set the setpoint mode to …
Main zone – Heating/Cooling
[A.3.1.1.1] Main > LWT setpoint
mode
Weather dep. OR WD/scheduled
Additional zone – Heating/Cooling
[A.3.1.2.1] Additional > LWT
setpoint mode
Weather dep. OR WD/scheduled
Tank
[A.4.6] Domestic hot water (DHW)
> SP mode
Weather dep.
To change the weather-dependent curve
Zone Go to …
Main zone – Heating [7.7.1.1]Main > Set weather-
dependent heating
Main zone – Cooling [7.7.1.2] Main > Set weather-
dependent cooling
Additional zone – Heating [7.7.2.1]Additional > Set
weather-dependent heating
Additional zone – Cooling [7.7.2.2] Additional > Set
weather-dependent cooling