10 | Configuration
Installer reference guide
154
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
# Code Description
N/A [9‑0D] Pump speed limitation additional zone
0: No limitation.
1~4: General limitation. There is limitation in all
conditions. The required delta T control and
comfort are NOT guaranteed.
5~8 (default: 6): Limitation when no actuators.
When there is no heating output, the pump
speed limitation is applicable. When there is
heating output, the pump speed is only
determined by delta T in relation to the
required capacity. With this limitation range,
delta T is possible and the comfort is
guaranteed.
The maximum values depend on the unit type:
[9-0D]=0 [9-0D]=1/5
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
[9-0D]=2/6 [9-0D]=3/7
[9-0D]=4/8
a (kPa)
b (l/min)
a External static pressure
b Water flow rate