3 | Specific installer safety instructions
Installer reference guide
17
ERLA11~16DAV3+W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation and are executed ONLY by authorised
persons.
Opening and closing the units (see
"7.2Opening and closing the units"[
4
78]
)
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
Mounting the outdoor unit (see
"7.3Mounting the outdoor unit"[
4
82]
)
WARNING
Fixing method of the outdoor unit MUST be in accordance with the instructions from
this manual. See "7.3Mounting the outdoor unit"[482].
Mounting the indoor unit (see
"7.4Mounting the indoor unit"[
4
86]
)
WARNING
Fixing method of the indoor unit MUST be in accordance with the instructions from
this manual. See "7.4Mounting the indoor unit"[486].
Piping installation (see
"8Piping installation"[
4
88]
)
WARNING
Field piping method MUST be in accordance with the instructions from this manual.
See "8Piping installation"[488].
DANGER: RISK OF BURNING/SCALDING
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.